Ohio Data Center

Electrical

Commercial Power - First Energy to Higbee Building Switch Gear at 11.400 Volts. These feeds are transformed down to 480 VAC at a 4000 Amp substation with 1600 Amp Main Breaker. This service is backed up with a 1200 Amp Automatic Transfer Switch (ATS) connected to a standby generator.

Generator - Caterpillar 800 kW (1,000 kVA) with 100-gallon day tank.

Fuel Storage - The generator fuel is provided from the base building fuel system of 5,000 gallons. Approximate run time is 72 hours.

UPS System - 225 kVA Liebert UPS, 10 minutes of minimum battery back up at full load, maintenance by-pass switch.

48 VDC Power - Provided upon request with requirements.

Surge Suppression - Liebert TVSS S1025277YANCN.

Telco Grounding - A facility main ground bar (MGB) is centrally provided and connected to the base building Telco ground system installed to meet Bellcore Telecom Standards

AC Grounding - All AC equipment grounded to separate grounding system.

Electrical Design Specification - 80 watts/SF.


Mechanical

CRAC Units - Glycol cooled with roof mounted dry coolers.Air Distribution is provided by branch ducts connected to a common plenum trunk.

Air Conditioning Design Specifications - 120 sensible btu/SF, N+1.

Fire Protection - NFPA Double Interlock Pre-action System.



Security
Base Building Security provides security guards, front security desk, cameras, video recording, 24/7 monitoring, card access, roving patrols and Fire Alarm monitoring.
ColloSource provides an additional independent security layer with local card key access, remote monitoring and video recording.

Cross Connection - Meet Me Room
Optical Cross Connection Frame.
Electrical Cross Connection Frame.Carriers & Telco Companies available at The Higbee Building
XO, WilTel, Dominion Telecom, AT&T and SBC.