Detroit Data Center
 Electrical
Commercial Power - Minimum 6000 Amps A/C @ 480 VAC, fed by two substations.
Generator - Two Katolite 1750 kW generator sets.
Fuel Storage - 1000 Gallon Double wall steel tank with 600 Gallon backup tank. Approximate run time is 72 hours.
UPS System - Provided upon request.
48 VDC Power - Redundant N+1 48V DC power plants
Surge Suppression - Leibert TVSS installed.
Telco Grounding - A facility main ground bar (MGB) is centrally provided and connected to the base building Telco ground system installed to meet Bellcore Telecom Standards.
AC Grounding - All AC equipment grounded to separate grounding system.
Electrical Design Specification - 70 watts/SF.
Mechanical
CRAC Units - G Glycol cooled with roof mounted dry coolers. 24 - 30 ton Leibert Model VE240G-AAEI HVAC units.
Air Conditioning Design Specifications - is provided by branch ducts connected to a common plenum trunk. 120 sensible Btu/SF, N+1
Fire Protection - NFPA Double Interlock Pre-action System.
Security Base Building Security provides security guards, front security desk, cameras, video recording, 24/7 monitoring, card access, roving patrols and Fire Alarm monitoring. ColloSource provides an additional independent security layer with local card key access, remote monitoring and video recording.
Cross Connection - Meet Me Room Optical Cross Connection Frame. Electrical Cross Connection Frame.Carriers & Telco Companies available at The Higbee Building XO, WilTel, Dominion Telecom, AT&T and SBC.
|
|
 |