Pittsburgh Data Center

Electrical

Commercial Power - Minimum 6000 Amps A/C @ 480 VAC, fed by two substations.

Generator - Two Katolite 1750 kW generator sets.

Fuel Storage - 1000 Gallon Double wall steel tank with 600 Gallon backup tank. Approximate run time is 72 hours.

UPS System - Provided upon request.

48 VDC Power - Redundant N+1 48V DC power plants

Surge Suppression - Leibert TVSS installed.

Telco Grounding - A facility main ground bar (MGB) is centrally provided and connected to the base building Telco ground system installed to meet Bellcore Telecom Standards.

AC Grounding - All AC equipment grounded to separate grounding system.

Electrical Design Specification - 70 watts/SF.


Mechanical

CRAC Units - G Glycol cooled with roof mounted dry coolers. 24 - 30 ton Leibert Model VE240G-AAEI HVAC units.

Air Conditioning Design Specifications - is provided by branch ducts connected to a common plenum trunk.
120 sensible Btu/SF, N+1

Fire Protection - NFPA Double Interlock Pre-action System.