Los Angeles 1
Los Angeles 2
Ohio
Michigan
Florida
Pennsylvania
 
Miami Data Center

Electrical

Commercial Power - FP&L, 480 VAC, 600 Amp Main Breaker backed up with an Automatic Transfer Switch (ATS) connected to a standby generator.

Generator - Cummins 500 kW with 200-gallon day tank.

Fuel Storage - The generator fuel is provided from the base building fuel system.

UPS System - 200 kVA

48 VDC Power - Provided upon request.

Surge Suppression - Joslyn TVSS #1456-85.

Telco Grounding - A facility main ground bar (MGB) is centrally provided and connected to the base building Telco ground system installed to meet Bellcore Telecom Standards.

AC Grounding - All AC equipment grounded to separate grounding system.

Electrical Design Specification - 70 watts/SF.


Mechanical

CRAC Units - G Glycol cooled with roof mounted dry coolers. 24 - 30 ton Leibert Model VE240G-AAEI HVAC units.

Air Conditioning Design Specifications - is provided by branch ducts connected to a common trunk duct

Fire Protection - NFPA Double Interlock Pre-action System.



Security
Base Building Security provides security guards, front security desk, cameras, video recording, 24/7 monitoring, card access, roving patrols and Fire Alarm monitoring.
ColloSource provides an additional independent security layer with local card key access, remote monitoring and video recording.

Cross Connection - Meet Me Room
Optical Cross Connection Frame.
Electrical Cross Connection Frame.Carriers & Telco Companies available at The Higbee Building
XO, WilTel, Dominion Telecom, AT&T and SBC.